24kW 30kVA Diesel Generator, Perkins 1103A-33G, Soundproof

24kW 30kVA Diesel Generator, Perkins 1103A-33G, Soundproof

Key Specifications / Features

The 24kW 30kVA Diesel Generator Set Factory offers a reliable and efficient power solution, ideal for both industrial and commercial use. It is powered by a Perkins 1103A-33G engine and paired with a Stamford PI124F alternator, delivering a consistent power output at 50 Hz. The generator operates at 400/230V with a maximum current of 43.3A. It maintains noise levels at 70 dBA from 7 meters, making it suitable for noise-sensitive areas.

Detail Information

Product Name: 24kW Perkins Soundproof Diesel Generator Set, Hot Sales
Fuel Type: Diesel
Engine: Perkins 1103A-33G
Alternator: Stamford PI124F
Rated Power: 24kW, 30kVA 
Maximum Power: 26.4kW, 33kVA 
Frequency: 50 Hz
Rated Voltage: 400/230 V
Rated Current: 43.3 A
Fuel Tank Capacity: 60 L
Noise Level (7m): 70 dBA
Battery for Starting: Two Maintenance-Free Batteries
Dimensions: 2050 * 900 * 1150 mm
Weight: 1050 kg


Engine Specifications (Perkins 1103A-33G)

 

Brand

Perkins

Model

1103A-33G

No. of Cylinders

3 (Inline)

Aspiration

Naturally Aspirated

Governor

Electric

Maximum Output Power

31 kW

Displacement

3.3 L

Compression Ratio

19.5:1

Starting Voltage

12 V

Bore

105 mm

Stroke

127 mm

Lubrication Oil Capacity

7.8 L

Intake Air Flow

2.16 m³/min

Fuel Consumption (100% Load)

7.1 L/h


Alternator Specifications (Stamford PI124F)

 

Brand

Stamford

Model

PI124F

Output Voltage

230/400V

Frequency

50Hz

Rated Current

Prime Power: 43A (30kVA)

Standby Power: 38A (33kVA)

Power Factor

0.8

Insulation Class

H

Protection Class

IP23

Efficiency

88.1%

Short Circuit Current

300% (10 sec)

Total Harmonic Distortion

Less than 2%

Connection Style

Phillips (Star)

Pole Number

4


Control Panel Specifications

 

Controller Brand

Smartgen

Controller Model

HGM6120

Breaker Brand

Delixi

Breaker Capacity

63 A

Battery Charger

Smartgen BAC06A

Emergency Stop Button

Supplied

Automatic Mains Failure (AMF)

Supplied

Fuel Level Monitoring

Supplied

Automatic Transfer Switch (ATS)

Optional

Optional Controllers

Deepsea, Smartgen, ComAp

Protections

Start-up Fault (Generator shutdown)

High Coolant Temperature (Alarm & Shutdown)

Low Oil Pressure (Alarm & Shutdown)

Low Fuel Level (Alarm)

Low Cooling Fluid Level (Optional Alarm)

Overload (Alarm & Shutdown)

Battery Voltage High/Low (Alarm)