73kW Diesel Generator Set, Perkins 1104A-44TG2, 60Hz, Silent

Key Specifications / Features
- Model No.: CGS-20250319-SGS-02
- Hits: 11
- Categories: Silent Generator Set
Detail Information
Product Name: 60 Hz Perkins Diesel Generator Set, Silent, 73kW (91kVA)
Fuel Type: Diesel
Engine: Perkins 1104A-44TG2
Alternator: Leroy Somer TAL-A44-D
Rated Power: 73kW, 91kVA
Standby Power: 80kW, 100kVA
Output Voltage: 133/230V
Frequency: 60 Hz
Power Factor: COSΦ=0.8 (Lagging)
Phase/Wires: 3 Phase, 4 Wires
Start Mode: Battery
Max Current: 144.3 A
Noise Level (7m): 70 dBA
Protection Features: Low Oil Pressure, High Water Temperature, Over-speed, Over-current
Engine Specifications (Perkins 1104A-44TG2)
Brand | Perkins |
Model | 1104A-44TG2 |
Cylinders | 4 |
Cycle | 4-Stroke |
Fuel Type | Light Diesel |
Compression Ratio | 17.25:1 |
Standby Power | 94kW |
Prime Power | 84.5kW |
Type of Injection | Indirect Injection |
Intake System | Naturally Aspirated |
Intake Resistance | ≤6.4 kPa |
Governor/Class | Mechanical |
Start Mode | DC24V Electric Start |
Cooling System | Water Cooled (Radiator) |
Cylinders Layout | Inline |
Displacement | 4.4 L |
Rated Speed | 1800 RPM |
Alternator Specifications (Leroy Somer TAL-A44-D)
Brand | Leroy Somer |
Model | TAL-A44-D |
Frequency | 60 Hz |
Phase | 3 Phase |
Windings | 100% Copper |
Exciter Type | Brushless |
Wiring | 12 Wires |
Terminals | 6 or 12 |
Insulation Class | H |
Altitude | ≤1000m |
Overspeed Limit | 2250 RPM |
Protection Class | IP23 |
Air Flow | 0.15 m³/s |
Frequency Fluctuation | ≤±0.5% |
Voltage Regulation | ±0.5% |
Voltage Distortion | < 4% |
Total Harmonic Distortion (TGH/THC) | < 4% |
Telephone Interference | THF< 2%, TIF< 50 |
Prime Power | 79.5kW, 99.4kVA |
Rated Voltage | 240V / 120V (Switchable) |
Frequency Regulation | ≤±0.5% (Stable) |
Voltage Control | AVR |
Control Panel Specifications
Controller Brand | Deepsea |
Controller Model | DSE7320 |
Breaker Brand | Delixi |
Breaker Capacity | 160 A |
Battery Charger | Smartgen BAC06A |
Emergency Stop Button | Supplied |
Automatic Mains Fail (AMF) | Yes |
Fuel Level Monitoring | Yes |
Automatic Transfer Switch (ATS) | Optional |
Protections | Start-up Fault (Shutdown) High Coolant Temperature (Alarm & Shutdown) Low Oil Pressure (Alarm & Shutdown) Low Fuel Level (Alarm) Low Coolant Level (Optional Alarm) Overload (Alarm & Shutdown) Battery Voltage High/Low (Alarm) |