Cummins Silent Diesel Generator Set, 200kW, 60 Hz, NT855-GA

Key Specifications / Features
- Model No.: CGS-20250327-SGS-02
- Hits: 12
- Categories: Silent Generator Set
Detail Information
Product Name: 200kW 250kVA Cummins Silent Diesel Generator Set
Fuel Type: Diesel
Engine: Cummins NT855-GA
Alternator: Stamford UCI274H
Rated Power: 200kW, 250kVA
Max. Power: 220kW, 275kVA
Frequency: 60 Hz
Rated Voltage: 220/127 V
Rated Current: 656.1 A
Noise Level: 70 dBA at 7m Away
Dimensions (L*W*H): 3200*1500*2010 mm
Net Weight: 2350 kg
Cummins Diesel Engine Specifications (NT855-GA)
Engine Brand | Cummins |
Engine Model | NT855-GA |
Number of Cylinders | 6 (Inline) |
Aspiration | Turbocharged |
Governor Type | Electric |
Max. Engine Output Power | 254 kW |
Displacement | 14.0 L |
Starting Voltage | 24 V |
Bore × Stroke | 140 mm × 152 mm |
Lubrication Oil Capacity | 38.6 L |
Stamford Alternator Specifications (UCI274H)
Alternator Brand | Stamford |
Alternator Model | UCI274H |
Rated Output | 255kVA |
Frequency | 60 Hz |
Insulation Class | Class H |
Altitude (Standard) | ≤1000 m |
Voltage Regulation | AVR Model SX460 |
Protection Grade | IP23 |
Optional Alternators | Leroy Somer, Marathon, Mecc Alte |
Control Panel Specifications
Controller Brand | Deepsea |
Controller Model | DSE7320 |
Breaker Brand | Delixi |
Breaker Capacity | 80 A |
Battery Charger | Smartgen Model BAC06A |
Emergency Stop Button | Yes |
Automatic Mains Failure (AMF) | Yes |
Fuel Level Indicator | Yes |
Automatic Transfer Switch (ATS) | Optional |
Control Panel Protection & Alarms
- Start-up Fault
- High Coolant Temperature
- Low Oil Pressure
- Low Fuel Level
- Overload
- Battery Voltage High
- Other protection features as required